Home > Armoured Cable > MV Cable >
MV Cable
AHXAMK-W Cable | AHXAMK-WM Cable | AHXAMK-WP Cable | |
Voltage Uo/U(Um) |
12/20 (24)kV 19/33 (36)kV |
12/20 (24)kV |
12/20 (24)kV 19/33 (36)kV |
Temperature Rating | -50°C to +90°C | ||
Max. conductor temperature during short circuit max. 5s | +250°C | ||
Minimum temperature during handling | -20°C | ||
Minimum temperature during transport | -40°C |
AHXAMK-W Cable | AHXAMK-WM Cable | AHXAMK-WP Cable | |
Conductor | Class 2 watertight, circular, stranded aluminium | ||
Conductor Screen | Semi conducting XLPE (Cross-Linked Polyethylene | ||
Insulation | XLPE (Cross-Linked Polyethylene) | ||
Insulation Screen | Semi conducting XLPE (Cross-Linked Polyethylene | ||
Metallic Screen | Aluminium/plastic laminate (Acts as a radial water barrier) | ||
Outer Sheath | PE (Polyethylene) | ||
Phase Support | Three sheathed cores laid up around a bare earth conductor | Waterproof round multi-threaded galvanised steel rope with weatherproof black PE plastic | - |
Outer Sheath Colour | Black |
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL CONDUCTOR DIAMETER | NOMINAL EARTH CONDUCTOR AREA SIZE | NOMINAL EARTH CONDUCTOR DIAMETER | NOMINAL DIAMETER OVER INSULATION WITHOUT SCREEN | NOMINAL INSULATION THICKNESS | NOMINAL THICKNESS OF ALUMINIUM LAMINATED FOIL | NOMINAL OUTER SHEATH THICKNESS | NOMINAL OUTER DIAMETER OF COMPLETE CABLE | NOMINAL WEIGHT |
mm2 | mm | mm2 | mm | mm | mm | mm | mm | mm | kg/km | |
3 | 50 | 8 | 35 | 6.9 | 19.3 | 5.5 | 0.2 | 2.8 | 59 | 2243 |
3 | 70 | 9.6 | 35 | 6.9 | 20.7 | 5.5 | 0.2 | 2.8 | 62 | 2531 |
3 | 95 | 11.1 | 25 | - | 22.4 | 5.5 | 0.2 | 2.9 | 66 | 2817 |
3 | 95 | 11.1 | 35 | 6.9 | 22.4 | 5.5 | 0.2 | 2.9 | 66 | 2905 |
3 | 120 | 12.6 | 35 | 6.9 | 23.4 | 5.5 | 0.2 | 2.9 | 68 | 3200 |
3 | 150 | 13.9 | 35 | 6.9 | 25.1 | 5.5 | 0.2 | 2.9 | 71 | 3570 |
3 | 185 | 15.6 | 35 | 6.9 | 27 | 5.5 | 0.2 | 3 | 76 | 4091 |
3 | 185 | 15.6 | 50 | 8.2 | 27 | 5.5 | 0.2 | 3 | 76 | 4191 |
3 | 185 | 15.6 | 70 | 9.9 | 27 | 5.5 | 0.2 | 3 | 76 | 4373 |
3 | 240 | 18 | 35 | 6.9 | 29.2 | 5.5 | 0.3 | 3.1 | 82 | 4868 |
3 | 240 | 18 | 70 | 9.9 | 29.2 | 5.5 | 0.3 | 3.1 | 82 | 5173 |
3 | 300 | 19.8 | 35 | 6.9 | 31 | 5.5 | 0.3 | 3.2 | 86 | 5603 |
3 | 300 | 19.8 | 70 | 9.9 | 31 | 5.5 | 0.3 | 3.2 | 86 | 5893 |
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL CONDUCTOR DIAMETER | NOMINAL AREA SIZE PHASE SUPPORT | NOMINAL DIAMETER OVER INSULATION WITHOUT SCREEN | NOMINAL INSULATION THICKNESS | NOMINAL THICKNESS OF ALUMINIUM LAMINATED FOIL | NOMINAL SHEATH THICKNESS | NOMINAL OUTER DIAMETER OF COMPLETE CABLE | NOMINAL WEIGHT |
mm2 | mm | mm2 | mm | mm | mm | mm | mm | kg/km | |
3 | 50 | 8 | 62 | 19.3 | 5.5 | 0.2 | 1.8 | 65 | 2257 |
3 | 70 | 9.6 | 62 | 20.7 | 5.5 | 0.2 | 1.9 | 69 | 2552 |
3 | 95 | 11.1 | 62 | 22.4 | 5.5 | 0.2 | 1.9 | 72 | 2882 |
3 | 120 | 12.6 | 62 | 23.8 | 5.5 | 0.2 | 2 | 75 | 3254 |
3 | 150 | 13.9 | 62 | 25.3 | 5.5 | 0.2 | 2 | 78 | 3568 |
3 | 185 | 15.6 | 62 | 26.8 | 5.5 | 0.2 | 2.1 | 80 | 4100 |
3 | 240 | 18 | 62 | 29.2 | 5.5 | 0.2 | 2.2 | 86 | 4815 |
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL CONDUCTOR DIAMETER | NOMINAL DIAMETER OVER INSULATION WITHOUT SCREEN | NOMINAL INSULATION THICKNESS | NOMINAL THICKNESS OF ALUMINIUM LAMINATED FOIL | NOMINAL SHEATH THICKNESS | NOMINAL OUTER DIAMETER OF COMPLETE CABLE | NOMINAL WEIGHT |
3x1 | 50 | 8 | 19.3 | 5.5 | 0.2 | 2.8 | 59 | 1939 |
3x1 | 70 | 9.6 | 20.7 | 5.5 | 0.2 | 2.8 | 62 | 2226 |
3x1 | 95 | 11.1 | 22.4 | 5.5 | 0.2 | 2.9 | 66 | 2598 |
3x1 | 120 | 12.6 | 23.4 | 5.5 | 0.2 | 2.9 | 68 | 2898 |
3x1 | 150 | 13.9 | 25.1 | 5.5 | 0.2 | 2.9 | 71 | 3268 |
3x1 | 185 | 15.6 | 27 | 5.5 | 0.2 | 3 | 76 | 3784 |
3x1 | 240 | 18 | 29.2 | 5.5 | 0.3 | 3.1 | 82 | 4563 |
3x1 | 300 | 19.8 | 31 | 5.5 | 0.3 | 3.2 | 86 | 5301 |