Home > Armoured Cable > MV Cable >
MV Cable
RHZ1-AL cable is a type of medium voltage halogen free power cable designed for fixed installations, typically used for power distribution in networks. The "RHZ1" designation indicates a flame-retardant, low-smoke cable, while "AL" specifies that it has an aluminum conductor. These cables are commonly used in environments where fire safety is crucial, such as transformer stations, infrastructure, and data centers. Where appropriate, waterblocking measures can be applied should it be installed in cable ducts liable to flooding. The suffix RHZ1-OL references a longitudinal waterblock applied above and below the screen, whilst a dual waterblock RHZ1-2OL has the longitudinal swellable tapes supplemented by swellable yarns or powders added to the conductor to make it watertight.
R | XLPE (Cross-linked Polyethylene) Insulation |
H | Semi conducting screen and metallic screen added. |
Z1 | Polyolefin compound |
OL | Longitudinal watertightness over the insulation screen only |
2OL | Longitudinal watertightness in conductor and over insulation screen |
(S) | Type 10E-4 (following HD620 Type 10E -4) |
(AS) | Type 10E-5 (following HD620 Type 10E -5) |
K | Compacted round shape conductor |
+H | Nominal Metallic screen cross sectional are in mm² |
AL | Aluminium Conductor |
RHZ1-AL Cable | RHZ1-OL-AL Cable | RHZ1-2OL-AL Cable | |
Voltage Rating Uo/U (Um) |
8.7/15 (17.5) kV 12/20(24) kV 18/30(36) kV |
||
Temperature Rating | -20°C to +90°C | ||
Minimum Bending Radius | 15 x overall diameter |
RHZ1-AL Cable | RHZ1-OL-AL Cable | RHZ1-2OL-AL Cable | |
CONSTRUCTION | Class 2 stranded aluminium | Class 2 stranded aluminium with longitudianal water tightness | |
Condutor Screen | Semi-conductive material | ||
Insulation | XLPE (Cross-Linked Polyethylene) | ||
Insulation Screen | Semi-conductive material | ||
Longitudinal Waterblocking | - | Water-swellable tape | |
Screen | Copper wires | ||
Sheath | PO (Polylefin) DMZ1 ST7 | ||
Sheath Colour | Red |
NO. OF CORES | NOMINAL CROSS SECTIONAL AREA | NOMINAL CONDUCTOR DIAMETER | NOMINAL INSULATION THICKNESS | NOMINAL DIAMETER OVER INSULATION | NOMINAL METALLIC SCREEN CROSS SECTION | NOMINAL OUTER SHEATH THICKNESS | NOMINAL OUTER DIAMETER | NOMINAL WEIGHT | |
8.7/15 (17.5)KV | mm2 | mm | mm | mm | mm2 | mm | mm | kg/km | |
1 | 50 | 8 | 4.5 | 18.2 | 16 | 2.5 | 28.1 | 720 | |
1 | 95 | 11.2 | 4.5 | 21.4 | 16 | 2.5 | 31.2 | 1100 | |
1 | 150 | 14 | 4.5 | 24.2 | 16 | 2.7 | 34.1 | 1440 | |
1 | 240 | 17.9 | 4.5 | 28.1 | 16 | 3 | 37.8 | 1780 | |
1 | 400 | 23.1 | 4.5 | 33.3 | 16 | 3 | 42.8 | 2300 | |
1 | 630 | 29.1 | 4.5 | 39.6 | 16 | 3 | 50.3 | 3190 | |
12/20 (24)KV | 1 | 50 | 8 | 5.5 | 20.2 | 16 | 2.5 | 28 | 850 |
1 | 95 | 11.2 | 5.5 | 23.4 | 16 | 2.7 | 32 | 1100 | |
1 | 150 | 14 | 5.5 | 26.2 | 16 | 3 | 34 | 1400 | |
1 | 240 | 17.9 | 5.5 | 30.1 | 16 | 3 | 38 | 1800 | |
1 | 400 | 23.1 | 5.5 | 35.3 | 16 | 3 | 43 | 2500 | |
1 | 630 | 29.1 | 5.5 | 41.6 | 16 | 3 | 50 | 3500 | |
18/30 (36)KV | 1 | 50 | 8 | 8 | 25.2 | 16 | 2.7 | 32 | 900 |
1 | 95 | 11.2 | 8 | 28.4 | 16 | 3 | 35 | 1200 | |
1 | 150 | 14 | 8 | 31.2 | 16 | 3 | 38 | 1500 | |
1 | 240 | 17.9 | 8 | 35.1 | 16 | 3 | 43 | 1900 | |
1 | 400 | 23.1 | 8 | 40.3 | 16 | 3 | 48 | 2750 | |
1 | 630 | 29.1 | 8 | 46.6 | 16 | 3 | 56 | 3500 |
As a professional cable manufacturer with decades of experience, Huadong Cable produces premium RHZ1-AL Cable that meet the highest industry standards. ✔ Fire Survival Performance – Maintains circuit integrity for 180+ minutes (IEC 60331 certified)
✔ Economic Conductivity – High-purity aluminum alloy with 61% IACS conductivity
✔ Enhanced Safety – LSZH (Low Smoke Zero Halogen) compound reduces toxic emissions
✔ Corrosion-Resistant – Special oxygen barrier layer prevents aluminum oxidation
For the RHZ1-OL-AL | RHZ1-2OL-AL Cable price, Please feel free to leave your requirement, We will reply you in 12 hours.
Hot Sales Medium Voltage Cable
Any cable inquiry please contact us.
huadong@hdcablegroup.com